Install wire and connect the air pressure sensors furnished system medical gas equipment columns as required after this equipment
| Tensile Strength | 8,900-10,500 PSI |
| Flexural | 13,500 PSI |
| Impact Strength, Izod | 14-17 ft/lb/in of notch |
| Hardness, (Rockwell) | M62-R118 |
| Melting Point | >300 degrees F |
| Burn Rate | <34 |
- Blower Cabinets and Ductwork
1. Each system shall include four (4) blower cabinets, to supply air to the special diffusers as indicated on plans. Blower cabinet shall house one (1) blower each.
2. Each blower shall be provided with a dedicated direct-drive 3/4 HP, 1075 rpm, high-efficiency fan motor. At full speed, each fan shall be rated to provide between 1500-1800 CFM while working against 1” w.g. static pressure.
3. The discharge velocity at the lower edge of the air containment shield at high speed shall be 80 ft./min. +/-10 ft./min.
- Each blower cabinet shall be suspended from the ceiling slab above by not less than four (4) ž” dia. threaded rods fastened to metal framing provided.
- Access to blower cabinets shall be by means of removable blank-off panels provided by manufacturer and located directly below each cabinet as shown on drawings.
- All blower cabinets and diffuser plenums shall be lined on the interior with 1” thick polyester urethane sound attenuating material with flame-bonded Tuftane coating on all exposed surfaces and when tested in compliance with ASTM Standard E-84-87, shall have a flame spread rating not to exceed 25 and a smoke developed rating not to exceed 50.
- Finish of blower cabinets shall identically match the finish of the special diffusers.
- Electrical Controls
1. Each system shall be provided with one (1) U.L. Label main electrical control cabinet with full color touch screen operator interface panel (OIP) surface-mounted on the control cabinet access door. A separate control box shall be provided to house an uninterruptible power supply (UPS). The electrical control cabinet shall house all control components necessary for 2-speed operation of the system, the overload protection devices, and the main system power disconnect. The control cabinet shall be wall-mounted within the operating room by the electrical subcontractor at a location determined by the owner. Location of UPS control box to be determined by owner.
2. Each system shall be provided with four (4) high efficiency, ū horsepower, 3-phase, 208/480 volt, direct-drive fan motors. The number of fan motors provided shall be based on the design criteria of the room. The owner shall provide one (1) ENGINEER TO SELECT VOLTAGE FROM ONE OF THE FOLLOWING AND DELETE OTHER TEXT:
- 30 Amp, 4-wire, 3-phase, 208 Volt
- 15 Amp, 4-wire, 3-phase, 480 Volt
power feeder from the emergency power system for each control cabinet.
- The control cabinet shall be 36” x 36” x 6” and fabricated from 14-gauge aluminum with a white powder-coat finish. The cabinet shall have 1” wide perimeter flange for flush mounting. The access door shall be hinged and grounded and shall be held closed by two quarter-turn fasteners. All controls components located within the panel shall be mounted on a 14-gauge aluminum back plate. The back plate shall have the same white powder-coat finish as the cabinet and shall be grounded.
- Speed control of each of the fans shall be provided by individual variable frequency drives (VFD’s) in conjunction with a single programmable logic controller (PLC). The VFD’s shall be used to set the speed for each fan motor in each mode during startup. Each VFD shall be provided with a supply line filter to prevent any reflected signal noise from interfering with the building’s power systems. All conduit containing power wires from the VFD’s to the motors shall be metallic and grounded to prevent the propagation of radio frequency interference (RFI).
- The PLC shall be factory programmed to switch the system between the high and low speed modes, to monitor the status of the fan motors, VFD’s and plenum air pressure sensors, and to relay all operational signal information between the OIP and the other control components. All operational commands and system mode changes input at the OIP shall be processed by the PLC to run the fan motors at the appropriate speed. Faults and alarms generated by the VFD’s or the pressure or temperature sensors shall be processed by the PLC to send the appropriate code to the OIP both notifying the user of the problem and aiding in troubleshooting. The PLC will also continuously monitor the system status and HEPA filter loading and send this information to the OIP to be displayed. An alarm relay is provided for fault communication with the building energy management system.
- Overload protection of the VFD’s, line filters, and the motors shall be provided by fusing at the main power disconnect and at each of the lines feeding the individual VFD’s. Fusing in the power feeds of each component shall provide protection of the step down transformer, the PLC, and the control side of the VFD’s. All components shall have positive grounding.
F. Lighting
- Lay-in style fluorescent light fixtures (nom. 2’x 4’ and/or 2’ x 2’ size) surrounding the diffusers shall be furnished, installed, and controlled by General Contractor’s electrical subcontractor.
FOR OPTIONAL TEARDROP PROFILE LIGHT FIXTURES INCLUDE PARAGRAPHS 2. & 3. BELOW:
- System shall include teardrop profile, single lamp lighting fixtures designed for cleanroom use between diffusers where shown on drawings. Fixtures shall be 24", 36", or 48" in length and 2" in width at the base. Fixture housing lamp holder brackets and channel cover shall be constructed of code gage steel. All metal parts shall be chemically treated with a rust resistant phosphatized solution and finish coating on reflective surfaces shall be white acrylic enamel electro-statically applied. The light diffuser shall be milk white acrylic linear prism. All electrical components shall be U.L. Listed. Fixture voltage shall be 120 Volt/Single Phase/60 Hz. Each fixture shall be provided with a 40-Watt lamp with a rapid start, high power factor ballast and radio frequency interference (RFI) suppressor. Mounting shall be to the bottom of 3" wide T-bar included in system’s suspension and support system.
- Installation, wiring, and control of the teardrop fixtures to shall be by General Contractor’s electrical subcontractor. Control responsibility to be determined by owner.
- BLANK-OFF PANELS
1. System shall include perforated blank-off panels identical in appearance to the panel diffusers for the following areas where columns may penetrate the ceiling or where interstitial access is required:
- surgical light column(s)
- medical gas column(s)
- other ceiling-mounted equipment column(s)
- access to blower cabinets
2. Blank-off panels shall have solid plate installed behind perforated plate, providing a seal between the room and interstitial space.
3. The installing contractor shall cut all fill-in panel(s) for the surgical light, medical gas, and/or other equipment column(s) as required after this equipment located.
---------------------------------------------------------------------------------------------------------------------------------------BLANK-OFF PANEL OPTION:
To specify SOLID BLANK-OFF PANELS, replace SECTION 2.3 PARA G. with the following:
1. System shall include solid face blank-off panels where indicated on the drawings and where columns may penetrate the ceiling or where interstitial access is required:
- surgical light column(s)
- medical gas column(s)
- other ceiling-mounted equipment column(s)
- access to blower cabinets
2. Panel to have solid plate installed within extruded aluminum perimeter frame with mitered corners providing a seal between the room and interstitial space.
3. The installing contractor shall cut all fill-in panel(s) for the surgical light, medical gas, and/or other equipment column(s) as required after this equipment located.
---------------------------------------------------------------------------------------------------------------------------------------
- support and Suspension System
1. The entire laminar flow system shall be suspended from the structure above. Support and suspension system shall include integral extruded aluminum tee and angle assembly to support air distribution modules, lighting fixtures, fill-in panels, and ceiling-mounted return air grilles. The minimum wall thickness of the aluminum tee shall be 0.125 inches with a minimum weight of 0.43 lbs./ft. The completed assembly shall be capable of supporting a load of 10 lb./sq. ft. The frame system to be either pre-cut and pre-assembled at the factory and marked for ease of reassembly in the field by the installing contractor or heliarc-welded at all intersection points at the factory into subassemblies not larger than 6’x18’ which butt to adjacent subsections for field assembly with "U" clips. All members shall be pre-punched on 6” centers for attachment for support hanger wires or ž” threaded rod to be attached on 2’-0” centers in two directions to strut support members.
2. Panel manufacturer shall furnish 1/8" thick closed cell polyethylene PSA-backed gasket tape to be field-installed onto the frame assembly.
3. Finish of the exposed ceiling level support and suspension system shall identically match the finish of the special perforated diffusers and blank-off panels.
- Each blower cabinet shall be suspended from the slab above by not less than four (4) ž” threaded rods attached on corners.
5. The system manufacturer shall furnish all P-1000 Unistrut members, ž” threaded rods, rod couplers, spring nuts & washers as necessary for structural support of the system as shown on system’s submittals.
6. Installing contractor shall furnish concrete anchors.
- RETURN AIR GRILLES WITH PREFILTERS
1. Manufacturer shall furnish ceiling-mounted return grilles where shown on drawings.
2. Manufacturer shall furnish two (2) sets of prefilters sized to fit return grilles with an ASHRAE Minimum Efficiency Reporting Value (MERV) number of 8 (or MERV-8 filters) in accordance with ASHRAE Std. 52.2.
- Finishes and Coatings
1. The complete tee and angle frame assembly, fan cabinets, return air grilles, diffusers and fill-in panels shall be finished in white baked enamel.
2. The finish on the aluminum trim around the entire perimeter of the air containment shield shall be 215-R1 clear anodized.
3. System to be provided with certification of all coatings and materials that have been furnished and installed.
PART 3 – EXECUTION
- Installation
A. Installation shall be by General Contractor’s sheet metal subcontractor at location shown on drawings. The General Contractor’s sheet metal subcontractor shall be responsible for the following:
- Installation of the Special High-Capacity Perforated Panel HEPA Diffuser Plenums, HEPA Filters (while under direct supervision by manufacturer’s personnel), Air Containment Panels, Blower Cabinets and Ductwork, Blank-Off Panels and Support & Suspension System.
- Furnish and install ductwork required for supply and exhaust of make-up air outside the surgical area as defined outside the perimeter of blower cabinets.
- Furnish concrete anchors and any additional structural support and hardware other than as recommended by system’s shop drawings and noted as “furnished by manufacturer”.
4. Removal of construction debris and cleaning of room to such state for owner’s final cleaning before testing and certification of system.
B. The General Contractor’s electrical subcontractor shall be responsible for the following:
- Furnish and connect the main power service to the system’s main control cabinet.
- Install wall-mounted main control cabinet for system.
- Wire and connect the blower motors to the system’s main control panel.
- Install, wire and connect the air pressure sensors furnished by system manufacturer to the main control cabinet from location within supply air plenums where shown on drawings.
- Furnish, install, connect and control any lay-in style fluorescent light fixtures surrounding the diffusers.
- Install, connect and control any optional teardrop light fixtures furnished as part of the system as located by submittal drawings.
- The system manufacturer shall supervise the installation of the system on an intermittent basis and provide start-up of the system. Factory-approved local representative shall be available for coordination meetings.
- PREPARATION FOR BALANCING, TESTING & CERTIFICATION
A. The General Contractor’s sheet metal subcontractor shall be responsible for removal of construction debris and initial cleaning of the room.
B. After the construction cleaning is complete, the owner shall be responsible for final sterilization of the rooms prior to the factory testing, balancing and certification phase of the project. The hospital’s normal sterilization procedure shall be followed in order to prepare the room for this phase.
3.3 BALANCING
- The manufacturer shall, after the unit has been installed, balance the system to obtain uniform airflow over the discharge face of the laminar flow diffusers in accordance with manufacturer’s recommended balancing procedures.
- TESTING AND CERTIFICATION
A. Upon completion of installation and sterilization of all rooms by owner, system manufacturer will supervise the installation of the filters and test, balance and certify the systems. The complete, balanced installation, while in the "High/Operating" Mode shall be certified by the manufacturer to be in compliance with Class 5 cleanroom standards as defined in Part 1 "Classification of Air Cleanliness" of ISO Standard 14644 titled "Cleanrooms and Associated Controlled Environments" (supercedes Federal Standard 209E titled "Airborne Particulate Cleanliness Classes in Cleanrooms and Clean Zones" where this same system shall meet Class 100 cleanroom conditions as defined as an area that must have less than 100 particles of 0.5 micron or larger size per cubic ft. of air).
B. At time of factory testing and certification, system manufacturer’s personnel will perform one (1) In-Service Training Session for the hospital’s operating staff and maintenance personnel. Manufacturer shall discuss overall system operation, answer questions regarding hospital’s protocol in relation to system operation, discuss filter replacement procedures, system troubleshooting and routine service, maintenance, and parts replacement procedures.
See all the reviews